· Regulatory control of offshore installations
The accident was instrumental in bringing about the Offshore Installations (Safety Case) Regulations. A safety case is a written document in which a company must demonstrate that an effective safety management system (SMS) is in place on a particular offshore installation. The implementation of this was handed over to the HSE in 1991.
· Adherence to Permit-to-Work System
This was a system of paperwork designed to promote communication between all parties affected by any maintenance procedure done on the platform. The system on Piper Alpha had become too relaxed. Employees relied on too many informal communications and communication between shift changes was lacking. If the system had been implemented properly, the initial gas leak never would have occurred.
· Quality of safety management is critical
The Cullen report on Piper Alpha was highly critical of the management system in the company. Managers had minimal qualifications, which led to poor practices and ineffective audits.
· Disabling of protective equipment by explosion
The firewalls on Piper Alpha could have stopped the spread of a fire. They were, however, not built to withstand an explosion. The initial blast blew the firewalls down, and the subsequent fire spread unimpeded
· Need for safety training
The workers on the platform were not adequately trained in emergency procedures, and management was not trained to make up the gap and provide good leadership during a crisis situation.
· Auditing is vital
Occidental Petroleum had regular safety audits of its facilities but they were not performed well. Few, if any, problems were ever brought up, even though there were serious issues with corrosion of deluge system pipes and heads and many other issues. When a major problem was found, it was sometimes just ignored.
· Proper isolation of plant for maintenance
The disaster would not have occurred if the pump where work was being done had been positively isolated. Isolation is not achieved by shutting a valve but requires means such as insertion of a slip plate or removal of a pipe section.
· Limit inventory on installation and in pipelines
The large inventory of the pipelines connected to the platform fed the fire. Despite technical problems, it should be a design objective to reduce the amount of hydrocarbons.
· Emergency Shutdown Valves
Proper location of emergency shutdown valves and backup valves are essential to cutting off fuel supply in case of a fire; above water positioning provides testing accessibility for vigilant maintenance.
· Fire and explosion protection
Protection against and mitigation of fire and explosion as well as fire fighting are of particular importance as there is no possibility to rely on outside assistance, such as the fire brigade.
· Temporary Safe Refuge (TSR)
TSR on each installation should have a breathable atmosphere through prevention of smoke ingress and provision of fire protection; escape routes and embarkation points should be determined through safety cases.
Prevention of smoke ingress into TSR is available through smoke and gas detectors that initiate smoke dampers and prevent circulation of smoke throughout the TSR.
· Evacuation and Escape
More than one route to helicopters and lifeboats must be present at any given time to ensure evacuation of the platform in a crisis situation. To facilitate escape from a hazardous situation, luminescent strips and heat shielding provide visibility in smoke and protection from flames, respectively. Secondary escapes such as ropes, ladders, and nets are also available as backup for the more sophisticated escape methods.
· Use of wind tunnel tests and explosion simulations in design
Wind tunnels are useful to assess the effectiveness of the ventilation and the gas detection system. The explosion simulations help investigate the effect of different layouts on explosion overpressures and assess the effectiveness of blast walls.